    Analytical study on prevention methods for distribution arrester outages caused by winter lightning

  • Author

    Nakada, K. ; Yokoyama, S. ; Yokota, T. ; Asakawa, A. ; Kawabata, T.

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    13
  • Issue
    4
  • fYear
    1998
  • fDate
    10/1/1998 12:00:00 AM
  • Firstpage
    1399
  • Lastpage
    1404
  • Abstract
    The effectiveness of lightning protection methods, such as lowering the grounding resistance and reducing the installation interval of surge arresters, for preventing damage to arresters on power distribution lines caused by direct lightning strokes in winter is investigated. Furthermore, several countermeasures for arrester outages which occur in spite of the installation of an overhead ground wire are studied quantitatively. The main results are as follows: (1) the installation of an additional overhead ground wire is more effective in preventing damage to arresters caused by winter lightning than increasing the withstand capability of arresters, by a factor of two; (2) and lowering the grounding resistance of arresters to 30 Ω is not effective in reducing the number of arrester outages
  • Keywords
    arresters; distribution networks; lightning protection; power system protection; direct lightning strokes; distribution arrester outages; grounding resistance lowering; lightning protection methods; overhead ground wire; surge arresters installation interval reduction; winter lightning; Arresters; Electric resistance; Grounding; Lightning protection; Power & Energy Society; Power distribution lines; Printing; Surge protection; Voltage; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.714514
  • Filename
    714514