DocumentCode
1426964
Title
Fault location using wavelets
Author
Magnago, Fernando H. ; Abur, Ali
Author_Institution
Dept. of Electr. Eng., Texas A&M Univ., College Station, TX, USA
Volume
13
Issue
4
fYear
1998
fDate
10/1/1998 12:00:00 AM
Firstpage
1475
Lastpage
1480
Abstract
This paper describes the use of wavelet transforms for analyzing power system fault transients in order to determine the fault location. Traveling wave theory is utilized in capturing the travel time of the transients along the monitored lines between the fault point and the relay. Time resolution for the high frequency components of the fault transients, is provided by the wavelet transform. This information is related to the travel time of the signals which are already decomposed into their modal components. The aerial mode is used for all fault types, whereas the ground mode is used to resolve problems associated with certain special cases. The wavelet transform is found to be an excellent discriminant for identifying the traveling wave reflections from the fault, irrespective of the fault type and impedance. EMTP simulations are used to test and validate the proposed fault location approach for typical power system faults
Keywords
fault location; power system analysis computing; power system transients; software packages; wavelet transforms; EMTP; computer simulation; fault impedance; fault location determination; fault transients; fault type; high frequency components; power system fault transients; signal travel time; transients travel time; traveling wave reflections; wavelet transforms; Fault location; Frequency; Monitoring; Power system faults; Power system relaying; Power system transients; Signal resolution; Transient analysis; Wavelet analysis; Wavelet transforms;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.714808
Filename
714808