DocumentCode :
1428256
Title :
Design and performance of active power filters
Author :
Thomas, Thierry ; Haddad, Kevork ; Joos, Geza ; Jaafari, Alain
Author_Institution :
MTE Corp., Mnomonee Falls, WI, USA
Volume :
4
Issue :
5
fYear :
1998
Firstpage :
38
Lastpage :
46
Abstract :
This article has demonstrated the feasibility of a three phase active filter based on a half-bridge topology. Design guidelines for the power circuit have been derived and applied to a 5 kVA IGBT laboratory prototype. In the single phase mode, the active filter can reduce the low frequency harmonic content in the AC line to below 1% excluding the harmonics due to switching action of the converter. In the three phase mode, line currents are corrected under balanced and unbalanced conditions. The neutral current is reduced significantly.
Keywords :
active filters; bridge circuits; compensation; insulated gate bipolar transistors; power filters; power system harmonics; 5 kVA; AC line; IGBT laboratory prototype; active power filters; balanced conditions; half-bridge topology; line currents correction; low frequency harmonic content reduction; neutral current; power circuit; single phase mode; three phase active filter; three phase mode; unbalanced conditions; Active filters; Capacitors; Power harmonic filters; Power quality; Power system harmonics; Proposals; Pulse width modulation; Topology; Voltage; Wire;
fLanguage :
English
Journal_Title :
Industry Applications Magazine, IEEE
Publisher :
ieee
ISSN :
1077-2618
Type :
jour
DOI :
10.1109/2943.715505
Filename :
715505
Link To Document :
بازگشت