• DocumentCode
    1428370
  • Title

    Study on Influence of Self-Generated Axial Magnetic Field Upon High-Current Vacuum Arc Behavior at a Long Contact Gap in High-Voltage Vacuum Interrupter

  • Author

    Cheng, Shaoyong

  • Author_Institution
    R&D Center, Shanghai Electr. Power T&D Group, Shanghai, China
  • Volume
    39
  • Issue
    3
  • fYear
    2011
  • fDate
    3/1/2011 12:00:00 AM
  • Firstpage
    911
  • Lastpage
    917
  • Abstract
    In this paper, the high-current vacuum arc characteristics under self-generated axial magnetic field (AMF) generated by a sinusoidal current flowing through the coil type of AMF contacts are investigated at long contact gaps of 40 and 60 mm. The distributing characteristics of the AMF in the contact gap are studied by a finite-element method, taking eddy current effect into account. Vacuum arc appearance was observed by a high-speed charge-coupled device video camera. The vacuum arc voltage was measured using a high-voltage probe. Capacitor and reactor (LC) discharging-current-interrupting tests were done with a single-frequency oscillating circuit. The vacuum arc behavior of a single coil-type AMF contact and that of a 1/2 coil-type AMF contact were compared. The research results show that both the amplitude and phase shift time of the AMF have great influence upon the high-current vacuum arc characteristics.
  • Keywords
    circuit breakers; finite element analysis; magnetic fields; vacuum arcs; vacuum interrupters; finite-element method; high-current vacuum arc behavior; high-voltage vacuum interrupter; long contact gap; self-generated axial magnetic field; sinusoidal current; Axial magnetic field (AMF); vacuum arcs; vacuum circuit breaker; vacuum interrupter;
  • fLanguage
    English
  • Journal_Title
    Plasma Science, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-3813
  • Type

    jour

  • DOI
    10.1109/TPS.2010.2098051
  • Filename
    5688477