DocumentCode :
1428584
Title :
Analysis of switching surges on a 220-kv line
Author :
Galiyano, M. C. ; Wagner, C. L. ; Hileman, A. R. ; Detty, V. C.
Author_Institution :
Pennsylvania Power & Light Company, Allentown, Pa.
Volume :
80
Issue :
7
fYear :
1961
fDate :
7/1/1961 12:00:00 AM
Firstpage :
524
Lastpage :
524
Abstract :
IN RECENT YEARS, improvements in lightning arrester characteristics have permitted reductions in transformer insulation levels and have led to extensive analysis and investigation of switching surges. Before the common use of reduced BIL transformers, switching surges were of no concern in most cases, since their magnitudes were well below the insulation strength of the windings. As transformer BIL is reduced, however, normal switching surges become a factor and arresters may be universally required for complete protection.
Keywords :
Arresters; Insulation; Power transformer insulation; Shape; Surges; Switches;