    Summary: Comparative performance of amplitude-comparator pilot-wire differential-protection systems

  • Author

    Gray, C.B.

  • Author_Institution
    University of Bradford, School of Electrical & Electronic Engineering, Bradford, UK
  • Volume
    121
  • Issue
    10
  • fYear
    1974
  • fDate
    10/1/1974 12:00:00 AM
  • Firstpage
    1180
  • Lastpage
    1182
  • Abstract
    A new relay circuit, applicable to asymmetrical pilot circuits, is described. In the steady state for relays at both ends, the circuit provides identical unit-diameter circular stability areas on the complex plane, centred on (1, 0), and it is suggested that this relay circuit constitutes a preferred characteristic of marginal operation. Certain alternative relay configurations are compared, to ascertain relative susceptibilities to the effects of induced interference voltages and the presence of d.c. components in the relaying quantities derived from the protected system. Homogeneous pilot circuits are assumed for simplicity, and the relay schemes considered include: (i) that referred to above which provides the preferred relay characteristic (ii) that which provides termination of the pilot circuit in characteristic impedance (iii) that which provides compensation for pilot-circuit phase-shift and a self-inverse characteristic.