DocumentCode
1430201
Title
Effect of humidity on sparkover of airgaps under impulsive voltages
Author
Allibone, T.E. ; Dring, D.
Author_Institution
Leeds University, Department of Electrical & Electronic Engineering, Leeds, UK
Volume
121
Issue
3
fYear
1974
fDate
3/1/1974 12:00:00 AM
Firstpage
221
Lastpage
222
Abstract
The influence of high humidity on the sparkover of a 40 cm square-ended rod-rod gap and round-ended rod-plane gap has been studied using impulse voltages of +1/1000 ¿S waveshape. Over the large humidity range 7¿27 g/m3 achieved, it was found that, for each increase of 1 g/m3 of water vapour, a corresponding increase in the mean sparkover voltage of 1% for the rod-rod gap and 1.25% for the rod-plane gap was obtained.
Keywords
humidity; impulse testing; spark gaps; airgaps under impulse voltages; effect of humidity; sparkover;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1974.0039