Power-factor compensation of thyristor-controlled single-phase load
Author :
Shepherd, W. ; Zakikhani, P.
Author_Institution :
University of Bradford, Postgraduate School of Studies in Electrical & Electronic Engineering, Bradford, UK
Volume :
120
Issue :
2
fYear :
1973
fDate :
2/1/1973 12:00:00 AM
Firstpage :
245
Lastpage :
246
Abstract :
It is found that an effective way to obtain a, good power factor with a thyristor-controlled load is to use a parallel-connected uncontrolled resistive load of similar rating. The use of parallel-connected capacitance alone gives no significant degree of power-factor improvement, even when the capacitance is adjusted to the optimum value for each step of thyristor firing angle.
Keywords :
load regulation; power factor correction; thyristor applications; voltage control; power factor compensation; thyristor controlled single phase load; voltage control;