DocumentCode
1430717
Title
Power-factor compensation of thyristor-controlled single-phase load
Author
Shepherd, W. ; Zakikhani, P.
Author_Institution
University of Bradford, Postgraduate School of Studies in Electrical & Electronic Engineering, Bradford, UK
Volume
120
Issue
2
fYear
1973
fDate
2/1/1973 12:00:00 AM
Firstpage
245
Lastpage
246
Abstract
It is found that an effective way to obtain a, good power factor with a thyristor-controlled load is to use a parallel-connected uncontrolled resistive load of similar rating. The use of parallel-connected capacitance alone gives no significant degree of power-factor improvement, even when the capacitance is adjusted to the optimum value for each step of thyristor firing angle.
Keywords
load regulation; power factor correction; thyristor applications; voltage control; power factor compensation; thyristor controlled single phase load; voltage control;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1973.0052
Filename
5251162
Link To Document