DocumentCode
1431411
Title
Sensitive ground-fault relaying
Author
Novak, Thomas ; Morley, Lloyd A. ; Trutt, Frederick C.
Author_Institution
Dept. of Mining Eng., Alabama Univ., AL, USA
Volume
24
Issue
5
fYear
1988
Firstpage
853
Lastpage
861
Abstract
Sensitive ground-fault protection refers to the concept of detecting low levels of ground-fault current that might cause electrocution of any human that becomes part of the ground-current path and providing warnings. The concepts behind sensitive ground-fault relaying for use on AC and DC low-voltage utilization systems are covered. The background for these relaying types is presented, and it is shown that the critical component in sensitive ground-fault relay design is the current sensor. Zero-sequence devices for three-phase industrial utilization systems and a saturable-transformer device for DC utilization are discussed. Relaying schemes for both AC and DC systems are presented. This study is aimed at mine power systems but could be applicable to any portable low-voltage portion of industrial power systems that involve handling by personnel
Keywords
mining; power system protection; relay protection; safety; current sensor; electrocution; ground-fault protection; industrial power systems; low-voltage utilization systems; mining; personnel; power system protection; relay protection; safety; Conductors; Electric resistance; Grounding; Hazards; Humans; Immune system; Mining industry; Power system protection; Protective relaying; Relays;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.8990
Filename
8990
Link To Document