• DocumentCode
    1431811
  • Title

    Spark ignition probability estimates for resistor and inductor circuits in methane-air atmospheres

  • Author

    Cawley, James C.

  • Author_Institution
    US Bur. of Mines, Pittsburgh Res. Center, PA, USA
  • Volume
    24
  • Issue
    5
  • fYear
    1988
  • Firstpage
    878
  • Lastpage
    883
  • Abstract
    The safety factor presently used by the US Mine Safety and Health Administration to assess the safety of electronic circuits for use in methane-air atmospheres is a factor of 1.5 on energy at the point of test plus two worst-case faults. The Bureau of Mines is engaged in intrinsic safety research that will ultimately relate the conditions of test and actual use by estimating the simple ignition probability, versus current for circuits in an 8.3% methane-air atmosphere. The experimental design minimizes the probability of not observing an ignition that should occur during a series of tests. For resistive circuits, no ignitions were observed below 2000 mA at 20 V DC, 350 mA at 30 V DC, 150 mA at 40 V DC, and 175 mA at 50 V DC. Results for inductive circuits show that ignition was not obtained below 35 mA for 600 mH, 90 mA for 100 mH, 230 mA for 10 mH, and 700 mA for 1 mH. These results imply that a threshold value exists below which spark ignition does not occur
  • Keywords
    ignition; mining; probability; safety; sparks; 150 mA; 170 mA; 20 V; 2000 mA; 230 mA; 30 V; 35 mA; 350 mA; 40 V; 50 V; 700 mA; 90 mA; USA; electronic circuits; ignition probability; inductive circuits; methane-air atmospheres; mining; resistive circuits; safety; spark ignition; Atmosphere; Circuit faults; Circuit testing; Electronic circuits; Electronic equipment testing; Health and safety; Ignition; Inductors; Resistors; Sparks;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.8994
  • Filename
    8994