A discussion of the WSCC 2 July 1996 outages
Author_Institution :
24 Buena Vista Ave., Scarborough, Ont., Canada
Abstract :
A criterion to distinguish between voltage instability and angle instability is presented. Analysis of the WSCC outage of 2 July 1996 is given. By applying the criteria, it is recognized that the Pacific Intertie outage was caused by angle instability. To avoid similar cascading outages, some related issues and suggestions are discussed. These include application of single phase tripping and reclosing, and improvements in dynamic performance monitoring.
Keywords :
monitoring; power system measurement; power system stability; Pacific Intertie outage; WSCC 2 July 1996 outages; angle instability; cascading outages; dynamic performance monitoring; single phase reclosing; single phase tripping; voltage instability; Automation; Automotive engineering; Costs; Load flow; Monitoring; Power engineering; Power engineering and energy; Sections; Vehicles; Voltage;