Abstract :
The fault performance of large generator units is considered in relation to the selection of generator-backup-protection settings, and a method of determining protection performance is presented, based on a simplified analysis of generator fault currents and neglecting rotor-angle swings. The validity of this approach is demonstrated and the method is used to determine the fault performance of negative-phase-sequence current and overcurrent protection. Alternative methods of overcurrent protection are examined which appear to provide improved backup protection for internal and external faults.
Keywords :
electric generators; overcurrent protection; power system protection; synchronous machines; fault currents; generator backup protection; generator fault currents; negative phase sequence current protection; overcurrent protection; synchronous machine performance during HV system faults;