DocumentCode :
1436308
Title :
Impulse-voltage breakdown of cold pressurised helium
Author :
Williams, B.G.
Author_Institution :
CEGB, Central Electricity Research Laboratories, Kelvin Laboratories, Leatherhead, UK
Volume :
121
Issue :
2
fYear :
1974
fDate :
2/1/1974 12:00:00 AM
Firstpage :
161
Lastpage :
164
Abstract :
Experiments on impulse breakdowns between uniform-field electrodes in helium are described. The breakdown fields of gaps from 1.27 to 6.35 mm are reported for helium conditions varying from 4.5 to 10 K and 0.395 to 0.82 MPa, corresponding to a density range from 25 to 140 kg m¿3. Comparisons with published direct-voltage breakdowns are made and the mechanisms discussed.
Keywords :
cable insulation; electric breakdown of gases; helium; cable; cold pressurised helium; impulse voltage breakdown;
fLanguage :
English
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
Publisher :
iet
ISSN :
0020-3270
Type :
jour
DOI :
10.1049/piee.1974.0028