DocumentCode :
1438870
Title :
Public-supply-system distortion and unbalance from single-phase a.c. traction
Author :
Howroyd, D.C.
Author_Institution :
Central Electricity Generating Board, Planning Department, System Technical Branch, London, UK
Volume :
124
Issue :
10
fYear :
1977
fDate :
10/1/1977 12:00:00 AM
Firstpage :
853
Lastpage :
859
Abstract :
A.C. traction loads cause the public supply voltage to be unbalanced on the three phases and distorted in waveform. These effects are potentially harmful, and it is necessary to understand and limit them in the interests of other parties. For this purpose, a method of prediction has been devised using the well known harmonic and phase-sequence components to make the calculation practicable. Although the manipulation of these components for single-phase traction supplies is complicated, prone to error and full of pitfalls, a simple method of calculation is illustrated.
Keywords :
electric distortion; harmonic analysis; load (electric); load regulation; power systems; traction; public supply system distortion; single phase AC traction loads; waveform distortion;
fLanguage :
English
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
Publisher :
iet
ISSN :
0020-3270
Type :
jour
DOI :
10.1049/piee.1977.0188
Filename :
5252830
Link To Document :
بازگشت