• DocumentCode
    1441043
  • Title

    General determination of rank and peak value of primary current harmonics in any 3-phase rectifier network

  • Author

    Bausi¿¿re, R. ; S¿¿guier, G.

  • Author_Institution
    Université des Sciences et Techniques de Lille, Villeneuve d´Ascq, France
  • Volume
    126
  • Issue
    11
  • fYear
    1979
  • fDate
    11/1/1979 12:00:00 AM
  • Firstpage
    1197
  • Lastpage
    1198
  • Abstract
    In a rectifier network, or group of such networks, fed by a 3-phase power supply, if the pulse number p of the rectified voltage is equal to 3 (or a multiple of 3), the primary currents have kp±1-rank harmonics only, k being an integer. In this paper, a general demonstration of this property is given, regardless of whether the load is infinitely inductive or not, and without ever specifying the diagram used. This demonstration gives an expression of the peak value of harmonics that makes them much easier to calculate when the rectified current undulation is not neglected.
  • Keywords
    harmonics; rectifying circuits; peak value; primary current harmonics; rank value; rectifier network; three phase;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Proceedings of the Institution of
  • Publisher
    iet
  • ISSN
    0020-3270
  • Type

    jour

  • DOI
    10.1049/piee.1979.0204
  • Filename