• DocumentCode
    1441125
  • Title

    Large transient neutral currents during energisation of 3-phase transformers

  • Author

    Pender, J.T. ; Kirkland, I.

  • Author_Institution
    University of Strathclyde, Department of Electrical Engineering, Glasgow, UK
  • Volume
    122
  • Issue
    4
  • fYear
    1975
  • fDate
    4/1/1975 12:00:00 AM
  • Firstpage
    369
  • Lastpage
    372
  • Abstract
    A magnetising inrush phenomenon characterised by a large exponentially decaying direct component of current in the neutral has been recorded in a number of 275 kV transformers. Laboratory investigations have shown that the effect can be produced in 3-limb transformers with certain combinations of nonsimultaneous energisation of the three phases. In particular, for the first two limbs to have their windings energised the sum of the fluxes in those limbs must be greater than the flux in the third limb when the third winding is energised. The initial magnitude of the d.c. component is proportional to the difference between these fluxes.
  • Keywords
    autotransformers; magnetisation; transients; autotransformer; energisation; large transient neutral currents; magnetising inrush phenomenon; three phase transformers;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Proceedings of the Institution of
  • Publisher
    iet
  • ISSN
    0020-3270
  • Type

    jour

  • DOI
    10.1049/piee.1975.0103
  • Filename