DocumentCode :
1441528
Title :
Identifying Transformer Inrush Current Based on Normalized Grille Curve
Author :
Ma, Jing ; Wang, Zengping ; Yang, Qixun ; Liu, Yilu
Author_Institution :
Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Beijing, China
Volume :
26
Issue :
2
fYear :
2011
fDate :
4/1/2011 12:00:00 AM
Firstpage :
588
Lastpage :
595
Abstract :
A novel algorithm for discrimination between inrush currents and internal fault currents by utilizing the normalized grille curve is proposed. First, the calculation method of the normalized grille curve is presented. Then, two schemes to discriminate the inrush currents from the internal faults in the time and frequency domains are, respectively, developed. A total of 268 experimental measurements have been tested on an YNd11-connected transformer. The results indicate that the proposed technique is able to reliably and accurately distinguish inrush currents from internal faults with easy implementation. Furthermore, the new method is not affected by the saturation of current transformers.
Keywords :
current transformers; fault currents; power transformers; YNd11-connected transformer; current transformers; internal fault currents; normalized grille curve; transformer inrush current; Circuit faults; Current transformers; Frequency domain analysis; Power transformers; Surge protection; Surges; Time domain analysis; Inrush currents; internal faults; normalized grille curve; power transformer;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2010.2101087
Filename :
5706395
Link To Document :