Correspondence: New approach to analysis of polarised mho relays under close-up-fault conditions
Author
Kandil, M.S.
Author_Institution
Mansoura University, Electrical Engineering Department Faculty of Engineering, Mansoura, Egypt
Volume
125
Issue
1
fYear
1978
fDate
1/1/1978 12:00:00 AM
Firstpage
56
Lastpage
58
Abstract
Under close-up-fault conditions the voltage signal from the faulty phase may not be sufficient to operate the mho relay. A voltage signal from one of the healthy phases, external polarisation, is added, and the relay, in this case, may be called an externally polarised mho relay. The main effect of external polarisation is the variation of the relay characteristic with the power-system conditions, which results in an increase of the resistive reach of the relay, under close-up fault condition. The paper introduces a new approach by which the resistive reach of externally polarised mho relays under close-up-fault condition could be evaluated without much analytical complexity and with reasonable accuracy.
Keywords
power system protection; relay protection; closed up fault condition; externally polarised mho relays; relay characteristic; voltage signal;