Abnormal currents in distribution transformers due to lightning
Author
Bryant, J. M. ; Newman, Mike
Author_Institution
University of Minnesota, Minneapolis, Minn.
Volume
61
Issue
8
fYear
1942
Firstpage
564
Lastpage
568
Abstract
Abnormal currents in distribution transformers due to lightning are analyzed both theoretically and from field experiences. Under certain conditions of direct stroke transferred through the arrester to the neutral of the secondary winding, excessive currents may wreck the secondary windings by electromagnetic forces. Long-duration surges, or shorter repeated surges, saturate the transformer cores producing greatly increased surge currents in the primary windings which influence fuse failures. The saturation of the cores by unidirectional lightning surges also brings about increased power-frequency magnetizing currents influencing sectionalizing-fuse and circuit-breaker operations.
Keywords
Circuit faults; Fuses; Lightning; Surge protection; Surges; Transformer cores; Windings;