Title :
Desert measurements of corona loss
Author :
Peterson, W. S. ; Cozzens, Bradley ; Carroll, Joseph S.
Author_Institution :
Department of Water and Power, The City of Los Angeles, Calif
Abstract :
THIS ARTICLE reports corona-loss measurements under desert conditions on 1.25-inch and 1.4-inch Hedernheim (HH) copper conductor and 1.4-inch aluminum-cable steel-reinforced (ACSR) conductor. From studies which have been conducted at Stanford University2,3 and subsequent theoretical analysis,4 it was indicated that 1.4-inch-diameter conductor would operate satisfactorily at 287 kv and that the segmental-type cable was more than sufficient for operation at 287 kv. This diameter initially had been established as a result of certain studies conducted on stranded-type cables.
Keywords :
Conductors; Corona; Laboratories; Loss measurement; Resistance; Temperature measurement; Transmission line measurements;
Journal_Title :
Electrical Engineering
DOI :
10.1109/EE.1950.6437042