• DocumentCode
    1450661
  • Title

    Combined phase and ground distance relaying

  • Author

    New, Warren C.

  • Author_Institution
    General Electric Company, Philadelphia, Pa.
  • Volume
    69
  • Issue
    11
  • fYear
    1950
  • Firstpage
    960
  • Lastpage
    960
  • Abstract
    ANEW relaying system provides complete phase- and ground-distance relaying protection for transmission lines. It features a reduction in the necessary equipment usually applied where three relays are connected to protect against faults involving 2- or 3-phase conductors, and where three relays are connected to protect against single-phase-to-ground faults. The reduction in equipment is achieved by causing the directional starting unit of the ground-distance relay to perform the double duty of detecting faults of a phase nature as well as faults of a ground nature.
  • Keywords
    Circuit breakers; Circuit faults; Current transformers; Electric potential; Relays; Timing; Windings;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1950.6437080
  • Filename
    6437080