Title :
Correlation between space charge distribution and water-tree location in aged XLPE cable
Author :
Suzuki, K. ; Tanaka, Y. ; Takada, T. ; Ohki, Y. ; Takeya, C.
Author_Institution :
Musashi Inst. of Technol., Tokyo, Japan
fDate :
3/1/2001 12:00:00 AM
Abstract :
The correlation between charge distribution in an aged crosslinked polyethylene (XLPE) cable and the location of water trees has been studied. The space charge radial distributions at different angle in the insulating wall of a service-aged XLPE coaxial cable, induced by application of a DC stress, were measured using the pulsed electroacoustic method. Furthermore, a cross section of sliced insulating wall was observed with an optical microscope to compare with the radial space charge distribution. The cable under investigation was electrically aged in service at 6.6 kV AC for 25 years in wet conditions. Water trees were found at the position in which space charge was observed. On the other hand, no water tree was found at the position in which the space charge was not observed. Judging from these results, the space charge measurement seems to be useful for the diagnosis of water trees in aged cables
Keywords :
XLPE insulation; charge measurement; insulation testing; power cable insulation; space charge; trees (electrical); 25 year; 6.6 V; DC stress; aged XLPE cable; optical microscopy; pulsed electroacoustic method; radial distributions; service-aged coaxial cable; sliced insulating wall cross section; space charge distribution; water tree diagnosis; water-tree location; Aging; Charge measurement; Coaxial cables; Current measurement; Optical microscopy; Polyethylene; Power cable insulation; Power cables; Space charge; Trees - insulation;
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on