DocumentCode :
1456658
Title :
Digital fault location for high resistance grounded transmission lines
Author :
Funabashi, Toshihisa ; Otoguro, Hitomi ; Mizuma, Yoshishige ; Kai, Takaaki ; Takeuchi, Nobutaka ; Akiyama, Satoko ; Dube, Laurent ; Ametani, Akihiro
Author_Institution :
Meidensha Corp., Tokyo, Japan
Volume :
14
Issue :
1
fYear :
1999
fDate :
1/1/1999 12:00:00 AM
Firstpage :
80
Lastpage :
85
Abstract :
This paper demonstrates that the presence of multiple load taps cannot be neglected for single-phase-to-ground fault location. A new method has been developed taking this into consideration, that can be applied to correct the location error due to intermediate power sources. Then fault location methods for parallel double-circuit two-terminal transmission lines are discussed. Finally, a new fault location method is proposed for high-resistance grounded double-circuit transmission lines with three terminals
Keywords :
earthing; fault location; power transmission faults; power transmission lines; digital fault location; high resistance grounded transmission lines; intermediate power sources; multiple load taps; parallel double-circuit two-terminal transmission lines; single-phase-to-ground fault location; three terminal transmission lines; Current measurement; Error correction; Fault location; Impedance; Power measurement; Power system faults; Power transmission lines; Transmission line measurements; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.736690
Filename :
736690
Link To Document :
بازگشت