DocumentCode
1456878
Title
Temperature classes for dry-type transformers
Author
Narbut, Paul
Author_Institution
Westinghouse Electric Corporation, Sharon, Pa.
Volume
72
Issue
7
fYear
1953
fDate
7/1/1953 12:00:00 AM
Firstpage
639
Lastpage
639
Abstract
INSULATING MATERIALS currently are classified into classes O, A, B, C, and H (AIEE Standard Number 1). Although this classification may be adequate as a rough indication of the nature of a material, it does not appear to be adequate for establishing standard operating temperature limits either for materials, or, particularly, for a complete apparatus. The inherent difficulties in establishing these limits are 1. The organic resins, which are used as a bonding agent in composite insulation, have a wide range of thermal stability. 2. The nature of the inorganic component (whether split mica or glass fiber) in composite insulation largely determines the aging properties of insulation, used as a dielectric barrier. 3. The function of the composite organic-inorganic material in the complete apparatus influences its life, whether a dielectric barrier, or just a spacer. 4. The mechanical arrangement of insulation influences its life, confined and supported, self-supporting, or acting as a mechanical support.
Keywords
Aging; Materials; Oil insulation; Power transformer insulation; Temperature;
fLanguage
English
Journal_Title
Electrical Engineering
Publisher
ieee
ISSN
0095-9197
Type
jour
DOI
10.1109/EE.1953.6438135
Filename
6438135
Link To Document