DocumentCode
1456961
Title
Water drop corona effects on full-scale 500 kV non-ceramic insulators
Author
Phillips, A.J. ; Childs, D.J. ; Schneider, H.M.
Author_Institution
Univ. of the Witwatersrand, Johannesburg, South Africa
Volume
14
Issue
1
fYear
1999
fDate
1/1/1999 12:00:00 AM
Firstpage
258
Lastpage
265
Abstract
It is shown that certain regions of commercially available 500 kV non-ceramic insulators have surface electric fields that are above the threshold for water drop corona. Observations made in a full scale accelerated aging chamber, and in service, demonstrate that water drop corona occurs on such insulators. A correlation between the magnitude of the surface electric fields and the condition of the silicone rubber non-ceramic insulator surfaces due to water drop corona is illustrated for two different insulator types in an accelerated aging chamber. Other examples of degradation of nonceramic insulators due to water drop corona are illustrated
Keywords
ageing; corona; drops; insulator testing; life testing; silicone rubber insulators; trees (electrical); 500 kV; full-scale accelerated aging chamber; in-service testing; insulator breakdown tests; nonceramic insulators; silicone rubber; surface electric fields; water drop corona effects; Accelerated aging; Africa; Ceramics; Corona; Degradation; Dielectrics and electrical insulation; Insulator testing; Power transmission lines; Rubber; Surface discharges;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.736734
Filename
736734
Link To Document