• DocumentCode
    1459136
  • Title

    Fast Protection of Strong Power Systems With Fault Current Limiters and PLL-Aided Fault Detection

  • Author

    Öhrström, Magnus ; Söder, Lennart

  • Author_Institution
    ABB Power Syst., Ludvika, Sweden
  • Volume
    26
  • Issue
    3
  • fYear
    2011
  • fDate
    7/1/2011 12:00:00 AM
  • Firstpage
    1538
  • Lastpage
    1544
  • Abstract
    In this paper, a new method is proposed that can be used to discriminate faults from switching transients. The method is primarily intended for use in systems where fast fault detection and fast fault clearing before the first peak of the fault current are required. An industrial system, in which high short-circuit power is desired but in which high short-circuit currents cannot be tolerated is an example of such a system. A phase-locked loop (PLL) is used to perform the discrimination. Computer simulations have been performed and it has been demonstrated that the output of the PLL is completely different for a fault compared to a switching transient. This difference can be used for discrimination between a fault and a switching transient.
  • Keywords
    fault current limiters; fault location; industrial power systems; phase locked loops; power system protection; short-circuit currents; switching transients; PLL-aided fault detection; fault current limiter; industrial power system; phase-locked loop; power system protection; short-circuit current; short-circuit power; switching transients; Circuit faults; Fault currents; Phase locked loops; Power systems; Switches; Transient analysis; Fault protection; phase-locked loop (PLL); power system; transients;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2011.2107530
  • Filename
    5720277