Title :
A new heavy-duty 3-phase oil circuit recloser
Author :
Van Ryan, Anthony
Author_Institution :
Line Material Company, Milwaukee, Wis.
fDate :
4/1/1953 12:00:00 AM
Abstract :
THE ECONOMIC DESIGN of automatic circuit reclosers has been made possible through the use of a series solenoid which opens the recloser when current exceeds a minimum trip value and stores energy for automatic reclosing. As the power output of the series solenoid at minimum trip current is small, this design has limited 3-phase reclosers to single-pole operation. Single-pole operation has the disadvantage that feedback through transformer banks can prevent the interruption of transient phase to ground faults and cause unnecessary lockout of the recloser.
Keywords :
Associate members; Current transformers; Delay effects; Interrupters; Oil insulation; Solenoids; Switches;