DocumentCode :
145976
Title :
High impedance fault location formulation: A least square estimator based approach
Author :
Ferraz, R.G. ; Iurinic, L.U. ; Filomena, A.D. ; Bretas, Arturo S.
Author_Institution :
Fed. Univ. of Rio Grande do Sul, Porto Alegre, Brazil
fYear :
2014
fDate :
March 31 2014-April 3 2014
Firstpage :
1
Lastpage :
4
Abstract :
The location procedure of HIF is a very difficult task and represents a great challenge for distance protection of transmission lines due to the under-reach and overreach effects. A new contribution for high impedance fault location for short transmission lines is proposed in this paper. The basic idea consists in solving an overestimated system using the method of the least square to locate the fault point. To evaluate the proposed approach, high impedance faults are simulated in a 100 km/230 kV transmission line. The test results show that the proposed approach has a high accuracy to locate HIF.
Keywords :
electric impedance; fault location; least squares approximations; power transmission lines; HIF; high impedance fault location formulation; impedance faults; least square estimator based approach; short transmission lines protection; Fault location; High impedance fault; least square;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection (DPSP 2014), 12th IET International Conference on
Conference_Location :
Copenhagen
Print_ISBN :
978-1-84919-834-9
Type :
conf
DOI :
10.1049/cp.2014.0046
Filename :
6822854