    Negative-sequence currents for line-to-line faults

  • Author

    Lawrence, R. F. ; Ferguson, R. W.

  • Author_Institution
    Westinghouse Electric Corporation, East Pittsburgh, Pa.
  • Volume
    72
  • Issue
    5
  • fYear
    1953
  • fDate
    5/1/1953 12:00:00 AM
  • Firstpage
    390
  • Lastpage
    390
  • Abstract
    THE RECENT REVISION of the American Standards Association Standard for Rotating Electrical Machinery, C50, short-circuit clause specifies requirements for synchronous generators during 3-phase, line-to-ground, and line-to-line short circuits. A generator operating at rated kilovolt-amperes and power factor, with fixed excitation at 5-per-cent overvoltage, must be able to withstand a 3-phase short circuit at its terminals. For line-to-ground short circuits, the maximum instantaneous current must not exceed that obtained under a 3-phase short circuit.