• DocumentCode
    146030
  • Title

    A novel energy ratio direction relay based on equivalent traveling wave process

  • Author

    Li Ren ; Xinzhou Dong ; Shenxing Shi ; Bin Wang

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • fYear
    2014
  • fDate
    March 31 2014-April 3 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Effective analysis method is required to analyze the entire traveling wave (TW) process, which includes the initial and succeeding TWs. As TW directional protection only uses the initial TWs to avoid potential confusion that may be caused by the aliasing of TWs, a long-term reliable criterion is difficult to offer. Thus, this paper proposes an analysis method for the whole TW process based on an equivalent TW process and a novel directional protection approach. Based on this equivalent TW process, the protection can overcome the limit of presenting long-term criterion, the problem of detecting a fault close to the relay location, and the insufficient sensitivity under the fault with an inception angle near zero that troubles the conventional TW directional protection. Extensive simulation of EMTP/ATP verified the performance of this protection.
  • Keywords
    fault diagnosis; power system faults; power system reliability; relay protection; EMTP-ATP simulation; energy ratio direction relay protection; equivalent TW process; equivalent traveling wave process; fault detection; inception angle; long-term reliability criterion; Duhamel integral; Long-term criterion; Protective relaying; Traveling wave process; Wavelet transform;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection (DPSP 2014), 12th IET International Conference on
  • Conference_Location
    Copenhagen
  • Print_ISBN
    978-1-84919-834-9
  • Type

    conf

  • DOI
    10.1049/cp.2014.0072
  • Filename
    6822880