Abstract :
Effective analysis method is required to analyze the entire traveling wave (TW) process, which includes the initial and succeeding TWs. As TW directional protection only uses the initial TWs to avoid potential confusion that may be caused by the aliasing of TWs, a long-term reliable criterion is difficult to offer. Thus, this paper proposes an analysis method for the whole TW process based on an equivalent TW process and a novel directional protection approach. Based on this equivalent TW process, the protection can overcome the limit of presenting long-term criterion, the problem of detecting a fault close to the relay location, and the insufficient sensitivity under the fault with an inception angle near zero that troubles the conventional TW directional protection. Extensive simulation of EMTP/ATP verified the performance of this protection.
Keywords :
fault diagnosis; power system faults; power system reliability; relay protection; EMTP-ATP simulation; energy ratio direction relay protection; equivalent TW process; equivalent traveling wave process; fault detection; inception angle; long-term reliability criterion; Duhamel integral; Long-term criterion; Protective relaying; Traveling wave process; Wavelet transform;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection (DPSP 2014), 12th IET International Conference on
Conference_Location :
Copenhagen
Print_ISBN :
978-1-84919-834-9
Type :
conf
DOI :
10.1049/cp.2014.0072
Filename :
6822880
Link To Document :
بازگشت