Abstract
A waste recycling and generation plant experienced significant power and frequency fluctuations following a steam valve closure on the generators prime mover. The reverse power protection did not remove the electrical machine from the network as quickly as expected, and concerns were raised regarding the resulting damage potential. This paper presents the modelling of the system and the improved reverse power protection function developed and tested using the model, to trip the machine within an acceptable period of time following such an event.
Keywords
power generation protection; steam turbines; synchronous machines; valves; waste-to-energy power plants; damage potential; electrical machine; frequency fluctuations; generation plant; generators prime mover; power fluctuations; reverse power protection; steam turbine valve closure; synchronous machine; waste recycling; Generation; Reverse power protection; Waste;