• DocumentCode
    1461511
  • Title

    Investigation of single unit flashovers in HVDC insulator strings

  • Author

    Ishikawa, Kouichi ; Kageyama, Hiroshi ; Yamada, Yasuhiro ; Matsuoka, Ryosuke ; Ito, Susumu ; Sakanishi, Kenji

  • Author_Institution
    Kansai Electr. Power Co. Inc., Osaka, Japan
  • Volume
    11
  • Issue
    4
  • fYear
    1996
  • fDate
    10/1/1996 12:00:00 AM
  • Firstpage
    1888
  • Lastpage
    1894
  • Abstract
    In HVDC transmission lines, a special phenomenon, so-called single unit flashover, is observed under some special conditions. Only one or two insulator units repeat flashovers, not resulting in an overall flashover along the string. However, higher magnitudes of audible noise, radio and television interferences may give a serious problem. Based on an investigation on ±500 kV full scale insulator strings, the higher occurrence probability of single unit flashovers under cold-wet-switch-on conditions was clarified compared with normal continuous operating voltage conditions. The effectiveness of the authors´ newly proposed countermeasures to prevent single unit flashovers was demonstrated by experiments in laboratory and in the field
  • Keywords
    HVDC power transmission; flashover; insulator testing; power transmission lines; 500 kV; HVDC insulator strings; HVDC transmission lines; audible noise; cold-wet-switch-on conditions; continuous operating voltage conditions; countermeasures; field tests; laboratory tests; radio interference; single unit flashover; television interference; Acoustic noise; Dielectrics and electrical insulation; Flashover; HVDC transmission; Indium tin oxide; Leakage current; Power transmission lines; Surface resistance; TV interference; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.544272
  • Filename
    544272