DocumentCode :
1461536
Title :
Improving feeder voltage calculation results with telemetered data
Author :
Leou, R.C. ; Lu, C.N.
Author_Institution :
Dept. of Electr. Eng., Nat. Sun Yat-Sen Univ., Kaohsiung, Taiwan
Volume :
11
Issue :
4
fYear :
1996
fDate :
10/1/1996 12:00:00 AM
Firstpage :
1914
Lastpage :
1920
Abstract :
A method that uses uncertain network data, load distribution information and telemetered data for feeder voltage profile calculation is proposed in this paper. In the proposed method, data involved in the calculation are represented by using fuzzy numbers. All possible feeder voltage solutions within bounds obtained from fuzzy arithmetic are considered. The mean values of the obtained intervals are useful for power system operation planning, and lower and upper bounds can be used to alert dispatchers for possible system deterioration. Measurements are included in the calculation to reduce the uncertainty of the obtained results. The voltage calculation method is used to evaluate the measurement configuration and a meter placement scheme is proposed to select the locations of new meters from the standpoint of minimizing the uncertainties of the calculated voltage profile
Keywords :
distribution networks; fuzzy set theory; load distribution; power system measurement; power system planning; telemetry; feeder voltage calculation; feeder voltage profile; fuzzy arithmetic; fuzzy numbers; lower bounds; mean values; measurement configuration; meter placement scheme; power system deterioration; power system operation planning; telemetered data; upper bounds; Arithmetic; Automation; Control systems; Fault diagnosis; Fuzzy systems; Reactive power; Testing; Uncertainty; Upper bound; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.544276
Filename :
544276
Link To Document :
بازگشت