A novel directional comparison pilot protection scheme based on Neutral-point Zero-sequence Current of UHV Auto-transformer
Author :
Kader, A. ; Xinzhou Dong ; Haiyun Wang ; Aini, Amingul
Author_Institution :
Sch. of Electr. Eng., Xinjiang Univ., Urumqi, China
fYear :
2014
fDate :
March 31 2014-April 3 2014
Firstpage :
1
Lastpage :
6
Abstract :
With the development of UHV power system, the capacity of autotransformer gets larger and zero-sequence impedance of autotransformer gets smaller accordingly. Therefore, the zero-sequence directional relay may mal-operate or misoperate due to the poor sensitive caused by the small zerosequence voltage, even the zero-sequence current threshold is reached. However, the large value of zero-sequence current of the neutral point in autotransformer is not utilized effectively. In view of this problem, this paper proposed a new method that using zero-sequence current of the neutral point in autotransformer instead of using two sides´ zero-sequence voltage of autotransformer to construct the novel zerosequence current directional protection scheme. Therefore, A Novel Directional Comparison Pilot Protection Scheme based on Neutral-point Zero-sequence Current of UHV Autotransformer is proposed in this paper. With the zero-sequence current of neutral point as reference, the fault direction can be determined by comparing the phase shift between zero sequence current of high voltage side, medium voltage side and the reference current. When the polarities of both sides are the same, the internal fault can be discriminated. When the polarities of both sides are different, the external fault can be discriminated. The proposed scheme eliminates the adverse effects yielded by zero-sequence voltage effectively. The miss-operation and refuse-operation problem of the traditional zero-sequence directional relay in UHV power system could be avoided.
Keywords :
autotransformers; fault currents; fault diagnosis; high-voltage techniques; power transformer protection; relay protection; UHV autotransformer; UHV power system; fault direction determination; mal operation; miss operation problem; neutral point zero sequence current; pilot protection scheme; refuse operation problem; zero sequence current directional relay protection scheme; zero sequence current threshold; zero sequence impedance; UHV Auto-transformer turn-to-ground; pilot protection; saturation of current transformer; turn-to-turn fault; zero-sequence current new direction components;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection (DPSP 2014), 12th IET International Conference on
Conference_Location :
Copenhagen
Print_ISBN :
978-1-84919-834-9
Type :
conf
DOI :
10.1049/cp.2014.0149
Filename :
6822957
Link To Document :
بازگشت