Abstract :
AN ECONOMIC DESIGN of pipe-type feeder has as small a pipe and as long a section as good engineering permits. Minimum pipe size must be large enough to insure that the top conductor, when in triangular formation, will not press against the pipe. If a clearance of 0.25 inch is calculated, using a conductor size with maximum tolerance, it is assumed that clearance is assured.