Influence of fault arc characteristics on the accuracy of digital fault locators
Author
Funabashi, Toshihisa ; Otoguro, Hitomi ; Mizuma, Yoshishige ; Dubé, Laurent ; Kizilcay, Mustafa ; Ametani, Akihiro
Author_Institution
Meidensha Corp., Tokyo, Japan
Volume
16
Issue
2
fYear
2001
fDate
4/1/2001 12:00:00 AM
Firstpage
195
Lastpage
199
Abstract
This paper proposes a time domain model of a fault locator with special reference to fault are nonlinearities by applying the MODELS language of the EMTP. It has been found that an impedance relay type locator is significantly influenced by the fault arc nonlinearities, while the current diversion ratio method is not influenced. This validates the advantage of the current diversion approach over the impedance approach
Keywords
EMTP; arcs (electric); fault location; power system faults; power system simulation; time-domain analysis; EMTP; MODELS language; computer simulation; current diversion approach; current diversion ratio method; digital fault locator accuracy; fault arc characteristics; impedance relay type locator; time domain model; Arc discharges; Circuit faults; Digital relays; EMTP; Fault location; Frequency domain analysis; Impedance; Power transmission lines; Protective relaying; Voltage;