• DocumentCode
    1464973
  • Title

    Approach to automatic contingency selection by reactive type performance index

  • Author

    Zhu, J.Z. ; Xu, G.Y.

  • Author_Institution
    Dept. of Electr. Eng., Chongqing Univ., Sichuan, China
  • Volume
    138
  • Issue
    1
  • fYear
    1991
  • fDate
    1/1/1991 12:00:00 AM
  • Firstpage
    65
  • Lastpage
    68
  • Abstract
    The authors present a novel approach to studying the automatic contingency selection (ACS). The total curtailment of the reactive loads is used as the performance index to evaluate the severity of contingencies. The minimum cost network flow model is proposed to determine the optimal curtailment in the line outage case. The objective of the model is the determination of the sum of branch voltage drops in terms of the line reactive flows. The optimisation model is solved by the out-of-kilter algorithm. The numerical results for several IEEE sample systems show that the proposed technique is feasible and effective
  • Keywords
    power systems; reactive power; ACS; automatic contingency selection; branch voltage drops; line outage; minimum cost network flow model; optimisation model; out-of-kilter algorithm; power systems; reactive loads; reactive type performance index;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    61655