Abstract :
In today´s power distribution systems, the protection methods do not provide full selectivity and instantaneous fault clearing for expected fault current, including lower-magnitude arcing currents simultaneously. This article discusses two methods that may change that. The first method is a selectivity analytical technique useful with many circuit breaker (CB) trips currently available in the industry. The second method is a new CB trip technology. Both methods allow switch gear CBs to use sensitive instantaneous settings and maintain selectivity when used in upstream current-limiting (CL) molded case CBs (MCCBs), CL motor circuit protectors (MCPs), or CL fuses in downstream equipment such as motor control centers (MCCs).
Keywords :
circuit breakers; circuit-breaking arcs; electric fuses; fault current limiters; power apparatus; power distribution protection; CB trip technology; CL fuse; CL motor circuit protector; MCCB; MCP; arc flash protection; arcing current; circuit breaker; current limiting molded case; downstream equipment; fault current; power distribution system; selectivity analytical technique; switchgear CB; Arc discharges; Circuit breakers; Circuit faults; Fault currents; Fuses; Sensors;
Journal_Title :
Industry Applications Magazine, IEEE