Abstract :
Modern circuit breakers (CBS) may be susceptible to catastrophic failure possibly because they are designed to be more highly stressed than earlier CB designs with multiple interrupters per pole. Improved performance is obtained with dielectrically well-designed interrupters by taking advantage of advanced controlled switching to achieve a reignition-free window during opening to minimize the risk of nozzle puncture. On occasion, CB owners may wish to check whether equipment is performing satisfactorily and whether controllers are producing reliable and repeatable stress control. The monitoring of voltage waveforms during switching using established methods will provide information about the magnitude and frequency of small reignitions and restrikes. However, waveform measurements at a moderately high signal frequency require plant outages to connect specialized equipment. A nonintrusive measurement technique has been developed to measure the high- and low-frequency voltage waveforms occurring during reactor switching operations without the need for an outage. Results of tests performed in the laboratory and in a 275-kV substation demonstrating the capability of this new method to detect reignitions are presented.
Keywords :
circuit breakers; interrupters; nozzles; power apparatus; reactors (electric); stress control; substations; voltage measurement; CB design; HV shunt reactor switching; advanced controlled switching; catastrophic failure; circuit breaker design; dielectrically well-designed interrupter; high-frequency voltage waveform measurement; low-frequency voltage waveform measurement; nonintrusive measurement technique; noninvasive method; nozzle puncture minimization; power equipment; reignition-free window detection; restriking detection; stress control; substation; voltage 275 kV; voltage waveform monitoring; Antenna measurements; Antennas; Inductors; Interrupters; Shunts (electrical); Switches; Transient analysis; Circuit breakers (CBs); controlled switching; restriking voltage sensors; shunt reactors; switching overvoltages;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2012.2185958