DocumentCode :
1471669
Title :
Optimizing generator reactive power resources
Author :
Adibi, M.M. ; Milanicz, D.P. ; Volkmann, T.L.
Author_Institution :
IRD Corp., USA
Volume :
14
Issue :
1
fYear :
1999
fDate :
2/1/1999 12:00:00 AM
Firstpage :
319
Lastpage :
326
Abstract :
A method is described for selecting generator step-up and auxiliary transformer tap positions to provide the desired reactive power requirements in a coal burning power plant. It is shown how a generator could be made to absorb reactive power, when previously unable to do so, by the adjustment of tap positions on the generator step-up and auxiliary transformers. The approach described provides an indication of the range of reactive power outputs that are available for different tap positions. This information would facilitate the alteration of transformer tap positions to make more effective use of generator reactive power resources
Keywords :
electric generators; machine theory; optimisation; power transformers; reactive power; steam power stations; auxiliary transformer tap positions; coal-burning power plant; generator reactive power resources optimisation; reactive power absorption; reactive power requirements; step-up transformer tap positions; Heating; Low voltage; Power generation; Power systems; Reactive power; Regulators; Stator cores; System buses; Temperature control; Voltage control;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.744550
Filename :
744550
Link To Document :
بازگشت