DocumentCode
1475240
Title
Methods to Minimize Zero-Missing Phenomenon
Author
Da Silva, Filipe Faria ; Bak, Claus Leth ; Gudmundsdottir, Unnur Stella ; Wiechowski, Wojciech ; Knardrupgård, Martin Randrup
Author_Institution
Inst. of Energy Technol., Aalborg Univ., Aalborg, Denmark
Volume
25
Issue
4
fYear
2010
Firstpage
2923
Lastpage
2930
Abstract
With the increasing use of high-voltage ac cables at transmission levels, phenomena, such as current zero missing, start to appear more often in transmission systems. Zero-missing phenomenon can occur when energizing cable lines with shunt reactors. This could considerably delay the opening of the circuit breaker (CB), leaving the system unprotected and vulnerable to failures. Methods to prevent zero-missing phenomenon are still being studied and compared in order to identify effective countermeasures. This paper contributes to these efforts by presenting several countermeasures that can be applied to reduce the hazards of zero-missing phenomenon. The authors discovered that this phenomenon can be eliminated, merely by using an extra CB or a preinsertion resistor.
Keywords
circuit breakers; power cables; switching transients; zero current switching; circuit breaker; high-voltage ac cables; preinsertion resistor; shunt reactors; zero-missing phenomenon; Cables; Circuit breakers; Delay; Hazards; Inductors; Resistors; Shunt (electrical); Switched capacitor circuits; Switching circuits; Voltage; AC circuit breaker (CB); level-crossing problems; power cables; shunt reactor; switching transients;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2010.2045010
Filename
5451167
Link To Document