  • Abstract
    With the increasing use of high-voltage ac cables at transmission levels, phenomena, such as current zero missing, start to appear more often in transmission systems. Zero-missing phenomenon can occur when energizing cable lines with shunt reactors. This could considerably delay the opening of the circuit breaker (CB), leaving the system unprotected and vulnerable to failures. Methods to prevent zero-missing phenomenon are still being studied and compared in order to identify effective countermeasures. This paper contributes to these efforts by presenting several countermeasures that can be applied to reduce the hazards of zero-missing phenomenon. The authors discovered that this phenomenon can be eliminated, merely by using an extra CB or a preinsertion resistor.
  • Keywords
    circuit breakers; power cables; switching transients; zero current switching; circuit breaker; high-voltage ac cables; preinsertion resistor; shunt reactors; zero-missing phenomenon; Cables; Circuit breakers; Delay; Hazards; Inductors; Resistors; Shunt (electrical); Switched capacitor circuits; Switching circuits; Voltage; AC circuit breaker (CB); level-crossing problems; power cables; shunt reactor; switching transients;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2010.2045010
  • Filename
    5451167