• DocumentCode
    1475290
  • Title

    Field tests and performance of heavy-duty high-speed 138-kv circuit breakers — Oil and air-blast

  • Author

    Sporn, Philip ; Clair, Harry P. St.

  • Author_Institution
    American Gas and Electric Service Corporation, New York, N. Y.
  • Volume
    64
  • Issue
    6
  • fYear
    1945
  • fDate
    6/1/1945 12:00:00 AM
  • Firstpage
    401
  • Lastpage
    410
  • Abstract
    The heavy expansion brought about on the Central System of the American Gas and Electric Company in response to demands for power during the defense and war periods has produced a requirement for circuit-breaker rupturing duties close to 3,500 megavolt-amperes. In order to test the interrupting performance and reliability of two types of 138-kv 3,500-megavolt-ampere circuit breakers, the first an oil, the second an air-blast design, and also to explore faster reclosing cycles than now offered by the most improved oil circuit breakers, high-capacity, field tests were carried out at the Philo Plant of The Ohio Power Company. In these tests, involving 20 interruptions on each breaker, there has been accomplished for the first time successful interruption of a full three-phase short circuit of 3,500 megavolt-amperes with three-cycle interruption and with 13-cycle reclosure. The results of these tests, it is believed, indicate that a goal of 5,000 megavolt-amperes with 12-cycle reclosure definitely is attainable.
  • Keywords
    Circuit breakers; Companies; Generators; Inductors; Layout; Magnetic circuits; Vents;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1945.6441082
  • Filename
    6441082