• DocumentCode
    1479581
  • Title

    Improved symmetrical component-based fault distance estimation for digital distance protection

  • Author

    Liao, Y. ; Elangovan, S.

  • Author_Institution
    Dept. of Electr. Eng., Nat. Univ. of Singapore, Singapore
  • Volume
    145
  • Issue
    6
  • fYear
    1998
  • fDate
    11/1/1998 12:00:00 AM
  • Firstpage
    739
  • Lastpage
    746
  • Abstract
    An improved symmetrical component-based method is proposed in the paper. The proposed method uses phasor estimates of voltage and current samples obtained from both ends of a power transmission line. The mathematical basis of the new approach is described. It is shown that the new method completely obviates complex arithmetic operations and has considerable computational advantages over the previously proposed methods. Furthermore, performance assessment studies on this new method using the alternative transient program (ATP) are presented and discussed. It is illustrated that the proposed method can determine the fault location very accurately and is likely to be used for digital distance protection and fault location
  • Keywords
    fault location; power transmission lines; power transmission protection; ATP; computational advantages; computer simulation; digital distance protection; fault distance estimation; fault location determination; performance assessment studies; power systems; power transmission line; symmetrical component approach;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19982366
  • Filename
    749177