Study on recovery time of a superconducting fault current limiter with adjustable trigger current level
Author
Shirai, Yasuyuki ; Fujikawa, Kazuhiro ; Kitagawa, Tomoyuki ; Shiotsu, Masahiro ; Hatta, Hiroyuki ; Muroya, Shiniti ; NItta, Tanzo
Author_Institution
Dept. of Eng. Sci. & Technol., Kyoto Univ., Japan
Volume
11
Issue
1
fYear
2001
fDate
3/1/2001 12:00:00 AM
Firstpage
2086
Lastpage
2089
Abstract
The recovery time of a transformer type SCFCL (superconducting fault current limiter) with adjustable trigger current level, is studied experimentally The recovery time is defined as the required time of zero current period of SCFCL for recovery from its current limiting mode to its waiting mode. A trial SCFCL, which was designed and made, is tested to measure the recovery time with various fault time. The experimental results show that the recovery time depends on the fault time. When the fault time is longer than 200 ms, the recovery time becomes shorter and approaches a certain value (a few ten ms) as the fault time is longer
Keywords
fault current limiters; superconducting coils; superconducting devices; adjustable trigger current level; current limiting mode recovery; fault time; recovery time; superconducting coils; superconducting fault current limiter; waiting mode; zero current period; Coaxial components; Current limiters; Fault current limiters; Fault currents; Power system analysis computing; Power system reliability; Superconducting coils; Superconducting filaments and wires; Testing; Time measurement;
fLanguage
English
Journal_Title
Applied Superconductivity, IEEE Transactions on
Publisher
ieee
ISSN
1051-8223
Type
jour
DOI
10.1109/77.920267
Filename
920267
Link To Document