    A single DC reactor type fault current limiting interrupter for three-phase power system

  • Author

    Usui, K. ; Nomura, T. ; Satoh, T. ; Yamaguchi, M. ; Fukni, S. ; Yokoyama, K. ; Nagasawa, T.

  • Author_Institution
    Niigata Univ., Japan
  • Volume
    11
  • Issue
    1
  • fYear
    2001
  • fDate
    3/1/2001 12:00:00 AM
  • Firstpage
    2126
  • Lastpage
    2129
  • Abstract
    The authors propose a single DC reactor type fault current limiting interrupter (FCLI) for a three-phase power system. The device uses a single high temperature superconducting (HTS) coil that operates in conjunction with a modified half control bridge composed of thyristors and diodes connected to a transformer´s secondary windings. One variety is an automatic interrupter, which automatically blocks fault current through the application of DC bias current to the bridge. Another is a gate interrupter, which does the same thing by locking the thyristor´s gate pulses. The authors examine the results of various simulations on a new device that both limits and interrupts fault current in a three-phase power system
  • Keywords
    fault current limiters; interrupters; power system protection; power transformers; superconducting coils; transformer windings; HTSC; automatic interrupter; diodes; fault current blocking; gate interrupter; high-temperature superconducting coil; modified half control bridge; single-DC reactor type fault current limiting interrupter; three-phase power system; thyristor gate pulse locking; thyristors; transformer secondary windings; Automatic control; Bridges; Fault currents; High temperature superconductors; Inductors; Interrupters; Power system faults; Power system simulation; Pulse power systems; Superconducting coils;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/77.920277
  • Filename