DocumentCode :
1481631
Title :
Simultaneous measurement of partial discharges using IEC60270 and radio-frequency techniques
Author :
Reid, A.J. ; Judd, M.D. ; Fouracre, R.A. ; Stewart, B.G. ; Hepburn, D.M.
Author_Institution :
Inst. for Energy & Environ., Univ. of Strathclyde, Glasgow, UK
Volume :
18
Issue :
2
fYear :
2011
fDate :
4/1/2011 12:00:00 AM
Firstpage :
444
Lastpage :
455
Abstract :
Partial discharge (PD) measurement is an established condition monitoring technique used to facilitate the detection of incipient faults in high voltage electrical insulation systems such as gas-insulated switchgear and power transformers. By simultaneously recording partial discharge using both the IEC60270 ´apparent charge´ measurement technique and the more recent Radio Frequency method, which measures the energy radiated from the discharge, it is thought that more information can be gained about the nature of the PD source. Combined measurement has been carried out on various common PD source topologies recreated under laboratory conditions using PD test cells in a range of insulating media including SF6, oil and epoxy resin. Test cell geometries include floating electrodes, free particles and protrusions. By plotting apparent charge against the energy of the RF signal for a large number of PD pulses, the relationship between the two techniques can be quantified for a given test configuration. It has been found that the correlation between the two techniques produces characteristic patterns specific to each defect type. It is envisioned that combined RF/IEC measurements will contribute to a more widespread acceptance of the RF technique in terms of its ability to quantify PD severity by relating the RF energy to the more widely accepted IEC60270 pC level.
Keywords :
IEC standards; UHF detectors; fault diagnosis; insulation; partial discharge measurement; power system measurement; IEC60270; PD measurement; RF-IEC measurement; condition monitoring technique; fault detection; floating electrode; free particle; gas-insulated switchgear; high voltage electrical insulation system; insulating media; partial discharge measurement; power transformer; protrusions; radio-frequency signal technique; test cell geometry; Charge measurement; Discharges; Partial discharges; Pulse measurements; RF signals; Radio frequency; Voltage measurement; IEC; Partial discharges; UHF detection; fault diagnosis; gas insulated switchgear; power system monitoring;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2011.5739448
Filename :
5739448
Link To Document :
بازگشت