    Study on Transient Recovery Voltages for Transformer-Limited Faults

  • Author

    Ito, H. ; Kajino, Hiroki ; Yamagata, Yoshiki ; Kamei, Kentaro ; Idemaru, Toshiki ; Shinkai, Hiromu

  • Author_Institution
    T&D Syst. Center, Mitsubishi Electr. Corp., Tokyo, Japan
  • Volume
    29
  • Issue
    5
  • fYear
    2014
  • fDate
    Oct. 2014
  • Firstpage
    2375
  • Lastpage
    2384
  • Abstract
    Severe transient recovery voltage (TRV) after current interruption may appear when a fault occurs in the immediate vicinity of a power transformer without any appreciable capacitance between the transformer and the circuit breaker. These faults are called transformer-limited faults (TLFs), that may cause higher rate of rise of TRV than the standard values specified for terminal fault test duties T10 and T30 of IEC 62271-100 and IEEE standard C37.06. TRVs for TLF conditions with large capacity and high-voltage shell-type power transformer were measured by the capacitor current injection method. The impedance frequency response were also measured by the frequency-response analysis (FRA) and then TRVs were reproduced by the simplified transformer model with a series connection of parallel circuit of inductance, capacitance, and resistance evaluated by the FRA measurements. The reproduced TRV showed good agreement with the measured TRV even though deformation from a sinusoidal waveshape was observed due to superposition of higher frequency components on the TRV.
  • Keywords
    fault diagnosis; frequency response; power transformers; FRA; FRA measurements; IEC 62271-100; IEEE standard C37.06; TLFs; TRV; capacitor current injection method; circuit breaker; frequency components; frequency-response analysis; high-voltage shell-type power transformer; impedance frequency response; large capacity shell-type power transformer; parallel circuit; sinusoidal waveshape; terminal fault test; transformer-limited faults; transient recovery voltages; Current measurement; Frequency measurement; Gain; Impedance; Power transformers; Resonant frequency; Transient analysis; Amplitude factor; circuit breaker (CB); frequency-response analysis (FRA); rate of rise of TRV; transformer-limited fault; transient recovery voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2014.2304968
  • Filename
    6750769