DocumentCode :
1486341
Title :
Design of Volts per Hertz limiter with consideration of the under-excitation limiter control actions
Author :
Jia, X.M. ; Choi, S.S.
Author_Institution :
Sch. of Electr. & Electron. Eng., Nanyang Technol. Inst., Singapore
Volume :
16
Issue :
2
fYear :
2001
fDate :
6/1/2001 12:00:00 AM
Firstpage :
140
Lastpage :
147
Abstract :
The dynamical relationship between the Volts per Hertz limiter and the under-excitation limiter control loops in a synchronous generator is examined using the frequency response technique. From the analysis, it is concluded that sustained oscillations due to the interaction between the two limiters can occur should the loading level of the generator exceeds a certain threshold value. For generator operation below this value, a systematic design procedure has been proposed for the limiters which will ensure network stability
Keywords :
control system analysis; control system synthesis; exciters; frequency control; frequency response; limiters; machine control; machine theory; oscillations; stability; synchronous generators; voltage control; Volts per Hertz limiter design; control loops; frequency response; loading level; network stability; sustained oscillations; synchronous generator; systematic design procedure; under-excitation limiter control actions; Control systems; Frequency response; Heating; Power generation; Reactive power; Stability; Stators; Steady-state; Synchronous generators; Voltage control;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.921465