  • Abstract
    UHF partial discharge detection in gas-insulated switchgear (GIS) has advantages over the conventional method. For example, UHF PD detection allows the suppression of high frequency disturbances external to the GIS. UHF PD measurements have been compared with measurements using the conventional IEC 270 method under conditions that approximate service conditions for a range of defects.
  • Keywords
    environmental testing; gas insulated switchgear; partial discharges; switchgear testing; IEC 270 method; PD detection; UHF; gas-insulated switchgear; high frequency disturbance suppression; partial discharge; service conditions; Electromagnetic measurements; Frequency; Gas insulation; Geographic Information Systems; IEC standards; Partial discharge measurement; Partial discharges; Performance evaluation; Switchgear; UHF measurements;