• DocumentCode
    1493664
  • Title

    Optimal computation of distance relays second zone timing in a mixed protection scheme with directional overcurrent relays

  • Author

    Pérez, Luis G. ; Urdaneta, Alberto J.

  • Author_Institution
    Univ. Simon Bolivar, Caracas, Venezuela
  • Volume
    16
  • Issue
    3
  • fYear
    2001
  • fDate
    7/1/2001 12:00:00 AM
  • Firstpage
    385
  • Lastpage
    388
  • Abstract
    This paper describes a technique to determine the optimal time setting for the second zone of distance relays when used in a mixed protection scheme with directional overcurrent relays. The technique consists of including the second zone operation time as a new variable in the original problem statement of optimal computation of directional overcurrent relays settings. It is shown that the influence of distance relays and directional overcurrent relays must be considered when the settings of these relays are computed. Numerical results obtained with the proposed method for a realistic power system are presented
  • Keywords
    overcurrent protection; power system faults; power system protection; power system relaying; relay protection; timing; directional overcurrent relays; distance relays second zone timing calculation; mixed protection scheme; power systems; problem statement; Circuit breakers; Circuit faults; Equations; Helium; Linear programming; Power system protection; Power system relaying; Protective relaying; Relays; Timing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.924815
  • Filename
    924815